Round and Rectangular Duct Equivalents

Round Diameter (in) Round Velocity (FPM) Round Area (sq ft) CFM Rect Area (sq ft) Rect Velocity (FPM) Rectangular Size (in)
44010.087350.1672106 × 4
54770.136650.1943347 × 4
65350.1961050.2224738 × 4
75990.2671600.34746110 × 5
86590.3492300.45850211 × 6
97130.4423150.50063012 × 6
107610.5454150.68161014 × 7
118110.6605350.83364215 × 8
128590.7856750.88975916 × 8
139060.9228351.12574218 × 9
149491.06910151.31976919 × 10
159941.22712201.38987820 × 10
1610381.39614501.68186322 × 11
1710791.57617001.91788723 × 12
1811181.76719752.00098824 × 12
1911581.96922802.257101025 × 13
2011992.18226152.62599627 × 14
2112352.40529702.722109128 × 14
2212732.64033603.021111229 × 15
2313102.88537803.444109731 × 16
2413463.14242303.556119032 × 16

Note: 6 × 4 represents the minimum practical rectangular duct size for most HVAC applications.

Standard Friction Rate Applications (0.1 in.w.g./100ft)

This friction rate is the industry standard for most residential and commercial HVAC systems. Provides a good balance between duct size, energy efficiency, and cost-effectiveness for typical installations.

Design Notes for 0.1 in.w.g./100ft Systems

  • Industry Standard: Most commonly used friction rate in residential and commercial applications
  • Balanced Design: Good compromise between duct size, energy use, and material costs
  • Moderate Velocities: Acceptable noise levels for most occupied spaces
  • Cost Effective: Smaller ducts than low-friction systems reduce installation costs
  • Versatile Application: Suitable for offices, retail, restaurants, and residential buildings
  • Energy Consideration: Higher friction than 0.08 systems increases fan energy slightly

Need Custom Duct Calculations?

Use our professional ductulator for instant calculations with any CFM, friction rate, or velocity.

Try the Calculator View 0.08" w.g. Chart